Overview
In alternating current (AC) power systems, calculating electrical quantities requires distinguishing between real power (measured in Watts), apparent power (measured in Volt-Amperes), and reactive power (measured in VAR). Because inductive loads such as electric motors, air conditioning compressors, and transformers shift current out of phase with voltage, apparent power is greater than real active power.
Safety Notice: Electrical calculator values are reference engineering estimates. Actual circuits require verifying phase balance, harmonic distortion, and conductor thermal ratings. Always consult the National Electrical Code (NEC) or local jurisdiction regulations and hire a licensed electrician.
Worked Examples
Single-Phase 230V 10A Motor with 0.8 Power Factor
Voltage = 230 V, Current = 10 A, Power Factor = 0.8, Single-phase AC.
- Calculate Apparent Power: S = 230 V × 10 A = 2,300 VA
- Calculate Real Power: P = 2,300 VA × 0.8 = 1,840 W
- Determine Phase Angle θ: arccos(0.8) = 36.87 degrees
- Calculate Reactive Power: Q = 2,300 × sin(36.87°) = 2,300 × 0.6 = 1,380 VAR
Final Answer: Real Power: 1,840 W | Apparent Power: 2,300 VA (Notice 2300 W is NOT real power)
Three-Phase 400V 10A Industrial Motor with 0.8 Power Factor
Voltage = 400 V line-to-line, Current = 10 A, Power Factor = 0.8, Three-phase AC.
- Apply Three-Phase Factor √3: √3 ≈ 1.7320508
- Calculate Apparent Power: S = √3 × 400 V × 10 A = 6,928.20 VA
- Calculate Real Active Power: P = 6,928.20 VA × 0.8 = 5,542.56 W
Final Answer: Real Power: 5,542.6 W (5.54 kW) | Apparent: 6,928.2 VA
Direct Current 24V 5A Solar Battery System
Voltage = 24 V, Current = 5 A, DC.
- In DC systems, Power Factor is identically 1.0
- Calculate Power: P = 24 V × 5 A = 120.0 W
Final Answer: P = 120.0 W (W and VA are identical)