Voltage Loss Calculator

While a voltage drop calculator determines how many volts are lost between a panel and an appliance, a Voltage Loss Calculator answers a different que

Electrical
A
Current flowing through conductors
ft
Distance from source to load
Copper conductor gauge
Single-phase loop vs three-phase conductors
h/day
Hours the circuit operates under load daily
$/kWh
Cost of electricity from your utility bill
Formula & Methodology
Power Loss (W) = I² × Rtotal; Energy Lost (kWh/yr) = (Power Loss ÷ 1000) × Hours/day × 365; Cost Lost ($/yr) = Energy Lost × Tariff Rate

Electrical power dissipation in conductors follows Joule's heating law: Power Loss = I² × R. Because power loss scales with the square of the current, doubling the amperage quadruples the heat dissipation. Total conductor resistance is computed from the number of current-carrying conductors (2 for single-phase, 3 for three-phase) and distance. Multiplying wasted kilowatts by annual operating hours and your utility rate reveals the financial cost of undersized wiring.

Continuous Conductor Power Loss (I²R Heat)

86.9 W Power Lost

Overview

While a voltage drop calculator determines how many volts are lost between a panel and an appliance, a Voltage Loss Calculator answers a different question: how much energy (kWh) and money are wasted as heat inside your building's wiring? Whenever current flows through conductors, I²R resistance dissipates electric power directly into walls and conduits.

Safety Notice: Electrical power loss calculations are reference estimates for financial and thermal efficiency analysis. They do not constitute code compliance certifications or engineering guarantees. Always consult the National Electrical Code (NEC) and hire a licensed electrician to evaluate conductor thermal limits.

Worked Examples

15A Continuous Load over 100 Feet with 12 AWG at $0.16/kWh

Current: 15A, Distance: 100 ft, 12 AWG copper (1.93 Ω/kft), 8 hours/day, $0.16/kWh.

  1. Total Conductor Resistance: 2 × (100 ÷ 1000) × 1.93 Ω = 0.386 Ω
  2. Calculate I²: 15 A × 15 A = 225 A²
  3. Calculate Power Dissipation: 225 A² × 0.386 Ω = 86.85 W
  4. Convert to Kilowatts: 86.85 ÷ 1000 = 0.08685 kW
  5. Calculate Daily Energy Lost: 0.08685 kW × 8 h = 0.6948 kWh/day
  6. Calculate Annual Energy Lost: 0.6948 × 365 = 253.6 kWh/year
  7. Calculate Annual Cost: 253.6 kWh × $0.16 = $40.58 / year
Final Answer: 86.9 W Lost | 253.6 kWh/yr wasted ($40.58/year lost)

Heavy 30A RV Feeder over 150 Feet with 10 AWG Copper

Current: 30A, Distance: 150 ft, 10 AWG copper (1.21 Ω/kft), 12 hours/day, $0.20/kWh.

  1. Resistance: 2 × 0.150 × 1.21 = 0.363 Ω
  2. Power Loss: 30² × 0.363 = 900 × 0.363 = 326.7 W
  3. Daily Energy: (326.7 ÷ 1000) × 12 = 3.92 kWh/day
  4. Annual Cost: 3.92 × 365 × $0.20 = $286.16 / year
Final Answer: 326.7 W Lost | $286.16/year wasted

Three-Phase 20A Industrial Line over 200 Feet with 8 AWG

Current: 20A, Distance: 200 ft, 8 AWG copper (0.764 Ω/kft), Three-phase (3 wires), 24 h/day, $0.12/kWh.

  1. Total Resistance (3 wires): 3 × 0.200 × 0.764 = 0.4584 Ω
  2. Power Loss: 20² × 0.4584 = 400 × 0.4584 = 183.36 W
  3. Annual Cost: (0.18336 × 24 × 365) × $0.12 = 1606.2 kWh × $0.12 = $192.75 / year
Final Answer: 183.4 W Lost | $192.75/year wasted

How to Use This Calculator

  1. Enter the design current in amperes flowing through the circuit.
  2. Enter the one-way distance in feet from panel to load.
  3. Select the copper wire gauge (AWG) and phase configuration.
  4. Enter daily operating hours and your local electricity rate per kWh.
  5. Click Calculate to see the continuous wattage lost as heat and annual cost.

Reference Table

Wire Gauge (AWG)Resistance (200 ft loop)Loss at 10 AmpsLoss at 20 AmpsLoss at 30 Amps
14 AWG0.614 Ω61.4 W245.6 WNot Recommended (Exceeds ampacity)
12 AWG0.386 Ω38.6 W154.4 WNot Recommended (Exceeds ampacity)
10 AWG0.242 Ω24.2 W96.8 W217.8 W
8 AWG0.153 Ω15.3 W61.2 W137.7 W
6 AWG0.098 Ω9.8 W39.2 W88.2 W

Frequently Asked Questions

What is the difference between voltage drop and voltage loss?
Voltage drop measures the reduction in electrical potential (volts) delivered to an appliance. Voltage loss (or conductor power loss) measures the actual energy (watts and kWh) dissipated as waste heat through wire resistance, and the financial cost on your electric bill.
Why does doubling the current quadruple the power loss?
Because power loss follows Joule’s law: P = I² × R. Power depends on current squared. Increasing current from 10A to 20A increases power dissipation by a factor of (20/10)² = 4 times.
Can upsizing wire gauge pay for itself over time?
Yes. In continuous commercial loads (like data centers, continuous pumps, or commercial lighting), stepping up from 12 AWG to 10 AWG reduces resistance by ~37%. The annual electricity savings often pay for the thicker copper within 2 to 4 years.
Does wire heat dissipation pose a fire hazard?
Excessive I²R heat in undersized or tightly bundled wires can degrade insulation and create a fire hazard. Electrical codes establish maximum allowable ampacities and conduit fill rules to keep wire temperatures below insulation ratings.
How do I find my electricity rate per kWh?
Check your most recent electric utility bill. Divide your total monthly charges by the total kilowatt-hours (kWh) consumed to determine your effective all-inclusive rate per kWh (typically $0.12 to $0.28 in the United States).
Reviewed & Authored by: OnlineConvers Engineering Editorial Team · Last Updated: 2026-10-07
Conductor power loss is calculated using Joule's heating law P = I²R_total, where R_total is determined from NEC Chapter 9 Table 8 conductor resistances at 75°C. Energy and financial projections apply linear multiplication across user-entered operating hours and utility tariffs. Thermal accumulation in conduit runs must be evaluated in accordance with NEC 310.16 derating guidelines.
Citations: Joule Heating and Thermal Management in Electrical Conductors (IEEE Transactions on Industry Applications) · Conductor Energy Efficiency and Life-Cycle Costing Standards (Copper Development Association (CDA))