Overview
Calculate room-by-room heating and cooling requirements in BTU/hr to size ductless mini-split indoor heads, hydronic baseboard radiators, or PTAC units. Every room function has unique thermal characteristics, from electronics in home offices to ovens in kitchens. Disclaimer: This calculator provides an estimate for preliminary sizing, budgeting, and equipment comparison based on standard industry rules of thumb; it does not replace an accredited ACCA Manual J residential load calculation performed by a licensed HVAC contractor.
Worked Examples
16 ft × 14 ft Living Room (9 ft Ceiling, Good Insulation)
Living room, 16 ft × 14 ft (224 sq ft), 9 ft ceiling, good insulation (1.00×).
- Calculate room floor area: 16 ft × 14 ft = 224 sq ft.
- Compute ceiling height ratio: 9 ft / 8 ft = 1.125×.
- Compute heating load: 224 sq ft × 40 BTU/hr/sq ft × 1.125 × 1.00 = 10,080 BTU/hr.
- Round heating load to nearest 100 BTU/hr: 10,100 BTU/hr.
- Compute cooling load: 224 sq ft × 20 BTU/hr/sq ft × 1.125 × 1.00 = 5,040 BTU/hr (rounded to 5,000 BTU/hr).
- Convert cooling to refrigeration tons: 5,000 ÷ 12,000 = 0.42 Tons.
- Estimate required airflow: 5,000 ÷ 30 ≈ 167 CFM.
- Recommended mini-split indoor unit head: 12,000 BTU/hr (covers 10,100 BTU/hr heating).
Final Answer: Heating: 10,100 BTU/hr | Cooling: 5,000 BTU/hr (0.42 Tons | 167 CFM)
14 ft × 12 ft Home Office with Computer Equipment
Home office, 14 ft × 12 ft (168 sq ft), 8 ft ceiling, good insulation (1.00×), +800 BTU/hr electronics.
- Calculate room floor area: 14 ft × 12 ft = 168 sq ft.
- Compute heating load: 168 sq ft × 38 BTU/hr/sq ft × 1.00 = 6,384 BTU/hr (rounded to 6,400 BTU/hr).
- Compute cooling load with electronics: (168 × 24) + 800 = 4,032 + 800 = 4,832 BTU/hr (rounded to 4,800 BTU/hr).
- Convert cooling to tons: 4,800 ÷ 12,000 = 0.40 Tons.
- Recommended mini-split head: 7,000 or 9,000 BTU/hr.
Final Answer: Heating: 6,400 BTU/hr | Cooling: 4,800 BTU/hr (0.40 Tons)
20 ft × 15 ft Finished Basement (8 ft Ceiling)
Basement, 20 ft × 15 ft (300 sq ft), 8 ft ceiling, good insulation (1.00×).
- Calculate room floor area: 20 ft × 15 ft = 300 sq ft.
- Compute heating load: 300 sq ft × 32 BTU/hr/sq ft × 1.00 = 9,600 BTU/hr.
- Compute cooling load: 300 sq ft × 14 BTU/hr/sq ft × 1.00 = 4,200 BTU/hr.
- Calculate cooling tonnage: 4,200 ÷ 12,000 = 0.35 Tons.
- Estimated airflow requirement: 4,200 ÷ 30 = 140 CFM.
Final Answer: Heating: 9,600 BTU/hr | Cooling: 4,200 BTU/hr (0.35 Tons)